NAVAL SERIES
General CharacteristicsThis unit was designed for any
naval
use
for continuous monitoring of insulation resistance to earth, on systems
connected to threephase without
neutral mains networks up to
240 V.
When the insulation resistance falls below the specified value (expressed in
kohm),
the device cuts in, activating an acoustic signal and an optical indicator.
Calibration is handled by a potentiometer located on the front enabling control
between 5 kohm
and 150 kohm;
a green LED (NORMAL) indicates the insulation status, a red LED (ALARM)
indicates fault status. There are also two push-buttons for TEST and RESET. Remote optical and acoustic indicators can be connected
to the terminal block, together with the routine check buttons for test and
reset. Assembly: OMEGA busbar - DIN EN 50022 Dimensions: width
315 mm (18 modules of step 17.5) COMPLIANCE WITH THE STANDARDS EN 61557-1; EN 61557-8 MEDICAL SERIES
General CharacteristicsThis
unit was designed for operating theatres for continuous monitoring of insulation
resistance to earth, systems connected to
monophase and threephase networks
up to 500 V with neutral insulated
from earth downstream of the insulation transformer. When
the insulation resistance falls below the specified value (expressed in kohm), the device cuts in, activating an acoustic signal
and an optical indicator. Calibration is handled by a potentiometer located on
the front enabling control between 50
kohm and 150
kohm; a green LED (NORMAL) indicates the insulation status,
a red LED (ALARM) indicates fault status. There are also two push-buttons for
TEST and RESET. Remote
optical and acoustic indicators can be connected to the terminal block, together
with the routine check buttons for test and reset. Assembly:
OMEGA busbar - DIN EN 50022 Dimensions:
width 157.5 mm (9 modules of step 17.5) COMPLIANCE WITH THE STANDARDS EN 61557-1; EN 61557-8 INDUSTRY SERIES
General CharacteristicsThis unit was designed for any industrial application
for continuous monitoring of insulation resistance to earth, on systems
connected to
monophase and threephase mains networks up to 500
V with neutral
insulated from earth downstream of the insulation transformer. When
the insulation resistance falls below the specified value (expressed in kohm),
the device cuts in, activating an acoustic signal and an optical indicator.
Calibration is handled by a potentiometer located on the front enabling control
between 5 kohm
and 150 kohm;
a green LED (NORMAL) indicates the insulation status, a red LED (ALARM)
indicates fault status. There are also two push-buttons for TEST and RESET. Remote optical and acoustic indicators can be connected
to the terminal block, together with the routine check buttons for test and
reset. Assembly: OMEGA busbar - DIN EN 50022 Dimensions: width 157.5 mm (9 modules of step 17.5) COMPLIANCE WITH THE STANDARDS EN 61557-1; EN 61557-8 BATTERY SERIES
General CharacteristicsThis unit is designed for continuous monitoring of the
insulation resistance to earth on 24
Vac or 24
Vdc equipment, for supplying scialytic lamps for
operating theatres or other Vdc users,
such as
photovoltaic plants. When
the insulation resistance falls below the specified value (expressed in kohm),
the device cuts in, activating an acoustic signal and an optical indicator.
Calibration is handled by a potentiometer located on the front enabling control
between 50 kohm
and 150 kohm;
a green LED (NORMAL) indicates the insulation status, a red LED (ALARM)
indicates fault status. There are also two push-buttons for TEST and RESET. Remote optical and acoustic indicators can be connected
to the terminal block, together with the routine check buttons for test and
reset. Assembly: OMEGA busbar - DIN EN 50022 Dimensions: width 157.5 mm (9 modules of step 17.5) COMPLIANCE WITH THE STANDARDS EN 61557-1; EN 61557-8 |
Send to